Key Points of Reefer Container Maintenance

A reefer (refrigerated) container consists of two separate systems: an insulated box and a refrigeration unit that cools it. Maintenance usually focuses only on the unit. Yet a significant share of temperature losses originates in the box.

The box: a silent point of loss

  • Insulation damage. Reefer walls are filled with foam insulation. A hole in the outer or inner panel lets moisture into this foam. Wet insulation permanently loses its effectiveness and makes the unit run harder. Holes should be repaired promptly, even small ones.
  • Interior lining. Interior panels (mostly stainless steel or aluminium) are damaged by forklift and cargo impacts. Damaged lining is a risk for both hygiene and insulation.
  • Door seals. A torn or hardened seal lets cold air escape continuously. Look from the inside with the door closed: if light is getting in, cold air is getting out.

Floor and airflow

The reefer floor consists of T-shaped channels (T-floor). Cold air circulates under the cargo along these channels. Packaging waste, labels or cargo residue that fill the channels block the airflow and create hot spots in the container. The floor should be cleaned after every unloading.

Drainage

Water formed at the evaporator and washing water are discharged through the drain holes in the floor and the drain kits. Blocked drainage causes water to collect inside the container and, over time, corrosion and bad odours. Whether the drain kits are working should be checked regularly.

Refrigeration unit

  • Pre-Trip Inspection (PTI). Before every loading, the unit is checked using the manufacturer’s test procedure. Sensitive cargo should not be loaded into a container that has not had a PTI.
  • Condenser cleaning. A condenser coil coated in dust and salt cannot reject heat. The unit uses more energy and struggles to reach the set temperature.
  • Data logging. The controller’s temperature records are the strongest evidence in any damage claim after the voyage. The records should be downloaded and kept regularly.
  • Refrigerant. By law, all work involving refrigerant (charging, leak repair) must be carried out only by personnel certified for it.

How does a reefer container work? Frequently asked questions

What is the refrigeration unit made of?

The refrigeration unit is an all-electric device fitted to the front wall of the container that can both cool and heat. Carrier’s PrimeLINE manual describes the unit in four sections: the compressor, which compresses the refrigerant gas; the condenser, which uses a fan to reject the gas’s heat outside; the evaporator, which cools or heats the air inside the container; and the control box holding the controller. The evaporator fans draw air from the top of the unit, pass it through the coil and discharge it at the bottom into the container, where the T-floor channels distribute it under the cargo.

How is a reefer powered?

The unit has its own power cable and plug; according to the same manual it runs on nominal 380/460 V, three-phase, 50/60 Hz power. On board ship and at the terminal the container is plugged into reefer sockets. Where there is no power connection, for example on the road, a generator set (genset) is used. Short power-offs are unavoidable: Hapag-Lloyd notes that there is normally no active cooling during gate-in and gate-out at the terminal or during loading and discharging.

How much energy does a reefer use?

There is no single figure; consumption depends on the set point, the outside temperature and the cargo. As a guide, the technical specification of Carrier’s 69NT40 unit gives the power drawn at full cooling capacity, at 38 °C ambient on a 60 Hz supply, as 10.8 kW at a +2 °C set point, 6.4 kW at −18 °C and 5.0 kW at −29 °C. Power is higher for chilled cargo because the unit removes far more heat at that temperature (cooling capacity 10,250 W at +2 °C versus 3,100 W at −29 °C). These are figures for demanding conditions; according to the same specification the unit adjusts its capacity once it reaches the set point (by suction modulation in chilled mode and by cycling the compressor on and off in frozen mode), so actual consumption varies over time.

How long can a reefer stay off power?

There is no fixed time; it depends on the type of cargo, its temperature when power is cut, the outside temperature and the sun. In CSIRO (Australia) trials with cartons of frozen beef, in a 40 ft container loaded at −18 °C the meat near the carton corners took about 42 hours to warm to −10 °C at 10 °C ambient, 22 hours at 25 °C and 13 hours at 40 °C; on a sunny summer day it took 19 hours. With the load starting at −14 °C the same times fell to 16, 8 and 5 hours. These results apply to frozen meat; chilled cargo such as fruit and vegetables must be assessed separately. Cargo weight matters too: to reduce temperature deviation during power-offs, Hapag-Lloyd recommends a minimum of 3,000 kg in a 20 ft reefer and 5,000 kg in a 40 ft reefer.

How noisy is a reefer?

Noise depends on the model and operating conditions. For example, Carrier states in the specification of its 69NT40 unit that noise measured 1.5 m in front of the unit and 1.2 m above the lower corner castings does not exceed 78 dB(A) at 380 V, 50 Hz. If a reefer will run close to homes or offices, ask the manufacturer or the lessor for the noise figure of the model to be used.

How is the temperature controlled?

The set point is entered on the unit’s keypad. The controller works with sensors measuring the air entering the evaporator (return) and the air leaving it (supply); in the example specification the control and recording range is −30 °C to +30 °C. With a set point above −10 °C (chilled mode) the unit continuously adjusts its capacity and heats if needed; below −10 °C (frozen mode) it cycles the compressor on and off. Ice that builds up on the evaporator is melted at intervals by electric heaters (defrost). The recorder stores at least one year of trip data. A reefer is used to maintain the cargo’s temperature; Hapag-Lloyd asks that the product be at the transport temperature before loading.

How does PTI (pre-trip inspection) differ between manufacturers?

PTI is an automatic test programme stored in the unit’s controller: it suspends normal operation, exercises the components one by one and gives a pass or fail result for each test. The logic is the same everywhere, but names, scope and duration differ by manufacturer:

  • Carrier (PrimeLINE): there are two automatic sequences. The short sequence (Auto/Auto1) runs tests P0 to P6 and covers most functions, sensors and components, but because they are lengthy tests it does not test the high-pressure switch, heater performance or cooling performance. The long sequence (Auto2: P0–P10, Auto3: P0–P8) adds them and is only available if enabled in the unit’s configuration. A failed test is repeated once. The optional TripWise function uses tests run in the background to judge whether a standard PTI is needed.
  • Thermo King (Magnum Plus, MP-4000): the Brief PTI and the Full PTI automatically test refrigeration and heating capacity, temperature control and the components, measuring the power drawn by the components and comparing it with expected values. According to the manual the Brief PTI takes about 25–30 minutes and the Full PTI up to 2–2.5 hours. There is also a functions test that checks the components only; a check mark on the display shows that a recently run SmartPTI found no problems.
  • Star Cool (Maersk Container Industry): with Intelligent Trip Inspection (ITI), offered since 2019, the manufacturer moves the check from the depot to the voyage: the unit diagnoses itself continuously while carrying cargo. According to the manufacturer, a container with a positive ITI check mark typically needs only a brief visual inspection and a routine wash before the next loading. The same article states that a traditional PTI at the depot often takes 2–4 hours or more, depending on conditions.

The automatic test is not enough on its own: alongside the PTI, Thermo King’s inspection table lists a visual check of the fans, electrical contacts and wire harnesses, a check of the refrigerant charge and an inspection of the unit for loose or broken parts. Carrier, for its part, states that a PTI should not be performed with critical temperature cargo in the container.

Should I rent or buy a reefer?

It depends on how long and for what purpose you will use it: renting is usually preferred for temporary or seasonal needs, buying for continuous use. When buying, check the condition of the box and the unit against the maintenance points above. Uskont rents and sells reefer containers; see our container rental and sales and purchase pages for details.

The box is a container too: Independently of the refrigeration unit, a reefer is subject to the same structural rules as other containers. Corner posts, rails, doors and the CSC plate are examined the same way for international transport.

Uskont carries out structural condition surveys and CSC examinations of reefer boxes. Servicing of the refrigeration unit is the job of the unit manufacturer’s authorised service partners. For a box examination, see our inspection service; to read a CSC plate, see our CSC guide.